| III | Input Conditions |
| | 3.1 | Normal input voltage operating range -- 22.0 volts 29.0 volts |
| | 3.2 | High input voltage shutdown -- shut down at input voltage in the range between 30 VDC and 32 VDC. |
| | 3.3 | Low voltage shutdown -- shut down at input voltage in the range between
18 VDC and 20 VDC. |
| |
| IV | Output Conditions |
| | 4.1 | Output RMS voltage - Factory set between 13.6 VDC and 13.8 VDC |
| | 4.2 | Output Regulation - < 0.1 V for all load values |
| | 4.3 | Output Ripple and Noise - < 50 mV RMS |
| | 4.4 | Output Current - 0 to 50 ADC continuous duty over the entire operating temperature range |
| |
| V | RF signal transparency |
| | 5.1 | High pass filters are encased in the converter to allow RF signals that are injected at the input terminals to pass freely to the output terminals in a frequency range ensuring PLC4 compatibility. |
| |
| VI | Protection mechanisms |
| | 6.1 | High input voltage shutdown @ 30-32 VDC |
| | 6.2 | Low input voltage shutdown @18-20 VDC |
| | 6.3 | Electronic short-circuit protection on output - will operate continuously into a short circuit without sustaining damage |
| | 6.4 | Input fuse protection on DC input side against reverse polarity connection |
| |
| VII | Cooling - Convection cooled |
| |
| VIII | Efficiency - Minimum of 89% at full load |
| |
| IX | Operating Altitude - 0 to 6,000 meters |
| |
| X | Humidity - 0 to 95% condensing |
| |
| XI | Operating Temperature - Minus 35C to plus 65C |